Practical guide · Water and wastewater

Pump Station Basics

By the end of this lesson

  • Follow water through a wastewater pump station
  • Explain how storage, pumps, valves, and controls work together
  • Distinguish a pump station from a Hydro-Brake flow control

A pump station adds energy to move water through pipes. A wastewater lift station raises sewage so that it can continue toward treatment. Water supply stations also use pumps to maintain pressure.

This guide follows a wastewater station. Drinking water stations need different hygiene controls and arrangements. The water and wastewater lesson explains those differences.

1Follow the water

  1. The inlet sewer brings wastewater to the station, usually by gravity.
  2. The wet well is a chamber that holds wastewater before pumping. Its water level rises as wastewater arrives.
  3. A level sensor measures the water level. The controller uses that signal to start and stop the pumps.
  4. The pump adds energy to the water. The force main is the pressurized pipe that carries it away.
  5. The receiving sewer or treatment process accepts the discharge. Its water level or pressure affects the work that the pump needs to do.

A station layout depends on the site. Some stations place submersible pumps in the wet well. Others keep the pumps in a separate dry chamber.

2Know the supporting equipment

Main parts of a wastewater pump station
PartPurpose
Screen or grinderA screen removes debris. A grinder cuts solids into smaller pieces. The station design determines which equipment it needs.
Check valveThis valve limits reverse flow through a stopped pump.
Isolation valveThis valve closes a pipe for maintenance. It serves a different purpose from a check valve.
Standby pumpThis pump provides backup capacity when another pump is unavailable.
Alarms and remote monitoringThese systems tell the operator about high water levels, power loss, or equipment faults.
Backup power or emergency storageThese provisions give the operator time to respond when normal power fails.
Access and lifting equipmentThese provisions let trained staff remove equipment for service.

3Understand a pump cycle

At the start level, the controller starts a pump. If pump discharge exceeds inflow, the water level falls. At the stop level, the controller stops the pump.

The working volume is the storage between those levels. Too little working volume causes frequent starts. Too much retained wastewater can increase odor problems.

Duty rotation changes which pump starts first. A standby pump can replace a failed pump. A high level alarm calls for attention before the water reaches a damaging level.

These functions depend on the actual control scheme. Read the wet well lesson and the controls, power, and safety lesson for the design details.

4Start a design with site information

Flow is the volume of water that passes each second. Head is energy per unit weight. A pump selection needs both.

  • Establish low, normal, and peak inflows. Include future demand and unwanted water that enters the sewer.
  • Record the source level and receiving level or pressure. Include the full operating range.
  • Record the pipe route, diameter, material, fittings, and valves. These determine the losses that the pump must overcome.
  • Define the capacity needed when equipment fails. Include alarms, backup power, emergency storage, and response time.
  • Use the manufacturer limits and the requirements of the local authority. Include access for cleaning and equipment removal.

The operating point is where pump output matches system demand. Lesson 7.2 shows why that point changes as water levels and pipe conditions change.

5Where a Hydro-Brake fits

A Hydro-Brake flow control restricts discharge from storage. It adds no energy and cannot replace the lift supplied by a pump.

Some drainage systems need both storage and pumping. The storage, outlet control, and pumps need one coordinated design. Restricting inflow can move the flood risk upstream.

Read the Hydro-Brake guide for the flow curve, storage relationship, and maintenance requirements.

Check your understanding

Make sure that you understand the station

3 auto-graded questions with an explanation for every wrong answer. Requires JavaScript. (pump-station-q1)

6Sources and further reading

The EPA lift station fact sheet, EPA 832-F-00-073 describes station equipment, controls, and reliability. It dates from September 2000. Use current local requirements for project decisions.

Continue with station anatomy, total dynamic head, and controls, power, and safety. These lessons develop the parts introduced here.

Introductory wastewater guide · Sources reviewed October 19, 2026