Concept reference
A variable frequency drive (VFD) changes motor supply frequency so pump speed can follow demand or level. It replaces throttling loss in suitable friction-dominated duties and softens many starts. It cannot erase static lift, and “variable” does not mean every speed is hydraulically or electrically acceptable.
Pump performance moves approximately by the affinity laws: Q ∝ N, H ∝ N², P ∝ N³ at corresponding points. Actual wire power also includes pump, motor and drive efficiency, each varying with load. Control must find the new intersection with Hsystem(Q).
A minimum-speed setting based only on motor capability can leave the pump below system static head, producing heat with little flow. Long motor leads, harmonics, bearing currents, reduced cooling and check-valve instability are equipment-specific concerns that a hydraulic energy calculation does not resolve.
§6.6 tests whether variable speed helps; §7.5 counts wire energy.
Physics sets the relationships; the owner, manufacturer and governing local standard set the project criteria.